3.0
2016-10-20T17:24:06Z
Smart-UPS X 3000
Smart-UPS X 3000 Monitoring
Smart-UPS X 3000 Monitoring
Monitoring of Smart-UPS X 3000 Battery Backups. SNMP OIDs from: http://www.itninja.com/blog/view/snmp-oids-for-apc-smart-ups-3000-rm-xl
Smart-UPS X 3000
UPS Connectivity
UPS Information
UPS Statuses
-
Ping Check
3
0
icmpping
60
27
27
0
3
0
0
0
0
1
0
0
Ping the device. We use this to prevent duplicate alerts. This will be the parent check for most other checks.
0
UPS Connectivity
Service state
-
Packet Loss
3
0
icmppingloss
60
27
27
0
0
%
0
0
0
0
1
0
0
Packet loss %.
0
UPS Connectivity
-
Response Time
3
0
icmppingsec
60
27
27
0
0
s
0
0
0
0
1
0
0
Response time.
0
UPS Connectivity
-
Battery Remaining Capacity
4
public
0
.1.3.6.1.4.1.318.1.1.1.2.2.1.0
SNMP-Battery-Capacity
60
27
27
0
3
%
0
0
0
0
1
0
0
161
Battery Charge Remaining, in %.
0
UPS Statuses
-
Battery Installation Date
4
public
0
.1.3.6.1.4.1.318.1.1.1.2.1.3.0
SNMP-Battery-Install-Date
86400
27
0
0
4
0
0
0
0
1
0
0
161
Battery Installation Date, M/D/Y.
0
UPS Information
-
System Model
4
public
0
.1.3.6.1.4.1.318.1.1.1.1.1.1.0
SNMP-Battery-Model
86400
27
0
0
4
0
0
0
0
1
0
0
161
APC Base System Model
29
UPS Information
-
Battery Run Time Remaining
4
public
1
.1.3.6.1.4.1.318.1.1.1.2.2.3.0
SNMP-Battery-RunTimeRemaining
60
27
27
0
0
Minutes
0
0
0
0
.00016666667
0
0
161
Battery Runtime Remaining, Minutes
0
UPS Statuses
-
Battery Supplying Voltage
4
public
0
.1.3.6.1.4.1.318.1.1.1.2.2.8.0
SNMP-Battery-Supplying-Voltage
60
27
27
0
0
V
0
0
0
0
1
0
0
161
Battery is Supplying Voltage, V
0
UPS Statuses
-
Battery Temperature (C)
4
public
0
.1.3.6.1.4.1.318.1.1.1.2.2.2.0
SNMP-Battery-Temperature
60
27
27
0
0
Degrees C
0
0
0
0
1
0
0
161
Battery Reported Temperature, C
0
UPS Statuses
-
Firmware Revision
4
public
0
.1.3.6.1.4.1.318.1.1.1.1.2.1.0
SNMP-Device-Firmware
86400
27
0
0
4
0
0
0
0
1
0
0
161
System Firmware Revision
5
UPS Information
-
Input Frequency
4
public
0
.1.3.6.1.4.1.318.1.1.1.3.2.4.0
SNMP-Device-Input-Frequency
60
27
27
0
3
Hz
0
0
0
0
1
0
0
161
System Power Input Frequency, Hz.
0
UPS Statuses
-
Input Voltage
4
public
0
.1.3.6.1.4.1.318.1.1.1.3.2.1.0
SNMP-Device-Input-Voltage
60
27
27
0
3
V
0
0
0
0
1
0
0
161
System Power Input Voltage, V
0
UPS Statuses
-
Output Frequency
4
public
0
.1.3.6.1.4.1.318.1.1.1.4.2.2.0
SNMP-Device-Output-Frequency
60
27
27
0
3
Hz
0
0
0
0
1
0
0
161
System Power Output Frequency, Hz.
0
UPS Statuses
-
Output Voltage
4
public
0
.1.3.6.1.4.1.318.1.1.1.4.2.1.0
SNMP-Device-Output-Voltage
60
27
27
0
0
V
0
0
0
0
1
0
0
161
System Power Output Voltage, V.
0
UPS Statuses
-
Serial Number
4
public
0
.1.3.6.1.4.1.318.1.1.1.1.2.3.0
SNMP-Device-Serial
86400
27
0
0
4
0
0
0
0
1
0
0
161
Serial Number
8
UPS Information
{Smart-UPS X 3000 Monitoring:SNMP-Battery-Capacity.avg(#5)}<1
Battery at 1% Charge, Failure Imminent @ {HOST.NAME}
0
5
The battery backup has <1% charge remaining on it.
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:SNMP-Battery-Capacity.avg(#5)}<10
Battery at 10% Charge @ {HOST.NAME}
0
4
The battery backup has <10% charge remaining on it.
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:SNMP-Battery-Capacity.avg(#5)}<25
Battery at 25% Charge @ {HOST.NAME}
0
3
The battery backup has <25% charge remaining on it.
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:SNMP-Battery-Temperature.avg(#5)}>36
Battery Temperature Excessive @ {HOST.NAME}
0
4
Battery Temperature CRITICAL (> 36 C/99 F).
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:SNMP-Battery-Temperature.avg(#5)}>30 and {Smart-UPS X 3000 Monitoring:SNMP-Battery-Temperature.avg(#5)}<36
Battery Temperature High @ {HOST.NAME}
0
3
Battery Temperature between 30-36 C (86-95 F). Normal 20-25 C (68-77 F).
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Voltage.last()}<10
Inbound Power Failure @ {HOST.NAME}
0
4
Power has failed to the APC unit.
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
({Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Voltage.avg(#5)}<100 or {Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Voltage.avg(#5)}>140 or {Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Frequency.avg(#5)}<50 or {Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Frequency.avg(#5)}>70) and {Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Voltage.last()}>0
Inbound Power Quality Warning @ {HOST.NAME}
0
3
Inbound power quality out of spec (>+/-15V, >+/-10Hz).
0
Inbound Power Failure @ {HOST.NAME}
{Smart-UPS X 3000 Monitoring:SNMP-Device-Input-Voltage.last()}<10
({Smart-UPS X 3000 Monitoring:SNMP-Device-Output-Voltage.avg(#5)}<100 or {Smart-UPS X 3000 Monitoring:SNMP-Device-Output-Voltage.avg(#5)}>140 or {Smart-UPS X 3000 Monitoring:SNMP-Device-Output-Frequency.avg(#5)}<50 or {Smart-UPS X 3000 Monitoring:SNMP-Device-Output-Frequency.avg(#5)}>70) and {Smart-UPS X 3000 Monitoring:SNMP-Device-Output-Voltage.last()}>0
Outbound Power Quality @ {HOST.NAME}
0
3
UPS is providing power outside normal range of values (+/-20V, +/-10Hz)
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:icmppingloss.min(5m)}>20
Ping loss is too high on {HOST.NAME}
https://zabbix.chatham-nj.org/tr_status.php?groupid=0&hostid=0
0
2
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:icmppingsec.avg(5m)}>2
Response time is too high on {HOST.NAME}
https://zabbix.chatham-nj.org/tr_status.php?groupid=0&hostid=0
0
2
0
{HOST.NAME} is unavailable by ICMP
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{Smart-UPS X 3000 Monitoring:icmpping.max(#3)}=0
{HOST.NAME} is unavailable by ICMP
https://zabbix.chatham-nj.org/tr_status.php?groupid=0&hostid=0
0
3
0
Service state
0
Down
1
Up